PERFORMANCE CORRELATIONS FOR COUNTERFLOW COOLING TOWER

Authors

  • Mohd Yusoff Senawi Faculty of Mechanical Engineering Universiti Teknologi Malaysia 81310 UTM Johor Bahru MALAYSIA

Keywords:

Counterflow cooling tower, Merkel theory, NTU, correlation

Abstract

The determination of outlet water temperature from a counterflow cooling tower when the tower NTU and inlet fluids conditions are known often involves a trial-and-error, iterative type of calculation. The standard Merkel’s theory has been used to predict tower outlet water temperatures for a range of values of independent variables: inlet water temperature, inlet air specific enthalpy, ratio of water to air mass flow rate and NTU. The results are used to develop correlations between outlet water temperature and the independent variables using multiple linear regression analysis. The simple correlations have errors that are lower than 2%. The predicted tower outlet water temperatures are within  0.65oC of those obtained from Merkel analysis.

References

Merkel, F. 1925. Verdunstungskuhlung. VDI Forschungsarbeiten, No. 275: 1–48.

Braun, J.E. 1989. Effectiveness Models for Cooling Towers and Cooling Coils. ASHRAE Trans. 95(2): 164–174.

Sutherland, J.W. 1983. Analysis of Mechanical-Draught Counterflow Air/Water Cooling Towers. Journal of Heat Transfer. 105(August): 576–583.

Stoecker, W.F. and Jones J.W. 1982. Refrigeration and Air Conditioning. New York. McGraw-Hill.

ASHRAE. 2000. ASHRAE Handbook – Systems and Equipment. Atlanta. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.

Yu, F.W. and K.T. Chan. 2008. Optimization of Water-Cooled Chiller System with Load-Based Speed Control. Applied Energy. 85: 931–950.

Yu, F.W. and K.T. Chan. 2009. Environmental Performance and Economic Analysis of all-Variable Speed Chiller Systems with Load-Based Speed Control. Applied Thermal Engineering. 29: 1721–1729.

ASHRAE. 1993. ASHRAE Handbook – Fundamentals. Atlanta. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.

Public Works Department of Malaysia. 2013. Building Energy Efficiency Technical Guide for Passive Design. Kuala Lumpur.

Downloads

Published

2018-04-01

How to Cite

Senawi, M. Y. (2018). PERFORMANCE CORRELATIONS FOR COUNTERFLOW COOLING TOWER. Jurnal Mekanikal, 39(1). Retrieved from https://jurnalmekanikal.utm.my/index.php/jurnalmekanikal/article/view/14