PERFORMANCE ANALYSIS OF A SPLIT TYPE ROOM AIR CONDITIONER
Keywords:
KeywordsAbstract
This paper investigates the performance of a split room air conditioner in the special-purpose
laboratory room. In order to evaluate the performance, an experimental set-up is constructed. The experimental components consist of a split room air conditioner which has, a hermetic
compressor, a condenser, an evaporator, capillary tube and two fans. For on-line reading
purposes , it uses data acquisition system and power meter. The unit is installed in the energy
conservation laboratory with the room volume of 16.8 m' at Faculty of Engineering, Universiti
Malaya, Kuala Lumpur. Experimental result is obtained for various ambient temperatures. The
electricity consumption and coefficient ofperformance ofthe system are measured and presented as a function ofthe ambient temperature.
References
ISO 5151, 1994, Non-ducted air conditioners and heat pumps-testing and rating for performance, 1sl ed. Geneva, Switzerland,
McQuiston, F.C. and Parker 1. D., 1994, Heating, ventilating, and air conditioning: analysis and design , 4th ed., John Wiley & Sons , New York.
Stoecker, W.F. and Jones, 1.W" 1982, Refrigeration & Air Conditioning. McGraw-Hill, Singapore.
Kent, E.F., 1997, Performance Evaluation of a Compact Air-To-Air Heat Pump, Energy Convers Mgmt, 38, 341.
Yokogawa, 1998, WTlIO/WT130 Digital Power Meter: User 's Manual, 3rd ed., Yokogawa Electric Company, Tokyo, Japan,
Downloads
Published
How to Cite
Issue
Section
License
Copyright of articles that appear in Jurnal Mekanikal belongs exclusively to Penerbit Universiti Teknologi Malaysia (Penerbit UTM Press). This copyright covers the rights to reproduce the article, including reprints, electronic reproductions or any other reproductions of similar nature.